Intelligent Fire Alarm Control Panels DN-7111. The ONYX® Series of Fire Alarm Controls from NOTIFIER. NFS-640, NCA, AFP-200, AFP-300/400, AFP-1010, and AM2020. NOTIFIER Network; Public Address. 1010/2020 Operators Manual. AFP-200 Operators Manual. download free 3sfe Repair Model Manual more. AFP-200(AUS) Installation & Programming Manual. AFP-2800 Manual NZ.

Looks like many of your questions have been answered, but here are my $0.02. As mentioned, the 'Earth Ground Fault in System Wiring' indicates a dead short to ground somewhere in the field wiring and is not related to the facility's grounding system. The best way to track down a ground fault is to disconnect all loops or circuits from the panel, and reconnect them one by one until the trouble comes in. Once you've identified which loop or circuit is causing the problem, it's sort of guess and check from there.

Notifier Afp 1010 Manual

You can go down the loop and disconnect/reconnect each device until the ground fault disappears. This will help you locate exactly which run of wire between two devices is causing the problem. Although the AFP1010 appears to control all buildings, each building may have it's own transponder (a remote keypad-less slave panel) that all circuits are connected to. In this case, the problem would have to be narrowed down to a specific node by disabling and enabling each transponder until the ground fault disappears, then proceeding to do as mentioned above for that transponder. I would recommend that all of this be done by a licensed technician since it can get pretty in-depth.

For the size of your facility, I don't think Fire-Lite or Silent Knight would be able to sufficiently handle your needs. download free Water Resources Engineering 2nd Edition Solution Manual. With multiple university buildings, you would be looking for a platform capable of networking and integrated mass notification. If budget permits, I would definitely recommend the with and. Also, the with.